产品参数
230kV双绕组无励磁调压电力变压器 | |||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range (kv) |
联结组 Connection symbol |
空载损耗 No-load loss (kw) |
负载损耗 Full-load loss (kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
|
高压 HV |
低压 LV |
||||||
31500 |
220 242±2×2.5% |
6.3 6.6 10.5 11 |
YNd11 | 35 | 135 | 12-14 | 0.70 |
40000 | 41 | 157 | 0.70 | ||||
50000 | 49 | 189 | 0.65 | ||||
63000 | 58 | 220 | 0.65 | ||||
75000 |
10.5 11 13.8 |
67 | 250 | 0.60 | |||
90000 | 77 | 288 | 0.55 | ||||
120000 | 94 | 345 | 0.55 | ||||
150000 |
11;13.8; 15.75;20 |
112 | 405 | 0.50 | |||
180000 | 128 | 459 | 0.46 | ||||
240000 | 160 | 567 | 0.42 | ||||
300000 |
15.75; 18;20 |
189 | 675 | 0.38 | |||
360000 | 217 | 774 | 0.38 |
低压为66kV级230kV双绕组无励磁调压电力变压器 | |||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range (kv) |
联结组 Connection symbol |
空载损耗 No-load loss (kw) |
负载损耗 Full-load loss (kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
|
高压 HV |
低压 LV |
||||||
31500 |
220 242±2×2.5% |
63 66 69 |
YNd11 | 38 | 151 | 12-14 | 0.89 |
40000 | 45 | 176 | 0.89 | ||||
50000 | 53 | 211 | 0.82 | ||||
63000 | 63 | 247 | 0.82 | ||||
90000 | 83 | 323 | 0.75 | ||||
120000 | 102 | 387 | 0.75 | ||||
150000 | 122 | 453 | 0.68 | ||||
180000 | 138 | 513 | 0.68 | ||||
240000 | 171 | 635 | 0.61 |
230kV双绕组有载调压电力变压器 | |||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range (kv) |
联结组 Connection symbol |
空载损耗 No-load loss (kw) |
负载损耗 Full-load loss (kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
|
高压 HV |
低压 LV |
||||||
31500 |
220 242±2×2.5% |
66.3;6.6 10.5;11 35;37;38.5 |
YNd11 | 38 | 135 | 12-14 | 0.70 |
40000 | 45 | 157 | 0.63 | ||||
50000 | 54 | 189 | 0.56 | ||||
63000 | 63 | 220 | 0.56 | ||||
90000 |
10.5;11 35;37;38.5 |
80 | 288 | 0.49 | |||
120000 | 99 | 346 | 0.49 | ||||
150000 | 116 | 405 | 0.42 | ||||
180000 | 135 | 468 | 0.42 | ||||
120000 |
66 69 |
102 | 355 | 0.49 | |||
150000 | 120 | 415 | 0.42 | ||||
180000 | 140 | 475 | 0.42 |
230kV三绕组无励磁调压电力变压器 | |||||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range(kv) |
联结组 Connection symbol |
空载损耗 No-load loss (kw) |
负载损耗 Full-load loss (kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
|||
高压 HV |
中压 MV |
低压 LV |
升压变 step-up |
降压变 step-down |
|||||
31500 |
220 242±2×2.5% |
69 115 121 |
6.3 6.6 10.5 11 35 37 38.5 |
YNyn0d11 | 40 | 162 |
高-中 H-M 22-24 高-低 H-L 12-14 中-低 M-L 7-9 |
高-中 H-M 22-24 高-低 H-L 12-14 中-低 M-L 7-9 |
0.70 |
40000 | 48 | 189 | 0.63 | ||||||
50000 | 56 | 225 | 0.56 | ||||||
63000 | 66 | 261 | 0.56 | ||||||
90000 |
10.5 11 13.8 35 37 38.5 |
86 | 351 | 0.49 | |||||
120000 | 106 | 432 | 0.49 | ||||||
150000 |
11 13.8 15.75 35 37 38.5 |
125 | 513 | 0.42 | |||||
180000 | 142 | 585 | 0.42 | ||||||
240000 | 176 | 720 | 0.35 | ||||||
300000 | 208 | 750 | 0.30 |
230kV三绕组无励磁调压自耦电力变压器 | |||||||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range(kv) |
联结组 Connection symbol |
空载损耗 No-load loss(kw) |
负载损耗 Full-load loss(kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
|||||
高压 HV |
中压 MV |
低压 LV |
升压 step-up |
降压 step-down |
升压 step-up |
降压 step-down |
升压变 step-up |
降压变 step-down |
|||
31500 |
220 242±2×2.5% |
115 121 |
6.6 10.5 11 35 37 38.5 |
YNyn0d11 | 25 | 22 | 117 | 99 |
高-中 H-M 12-14 高-低 H-L 8-12 中-低 M-L 14-18 |
高-中 H-M 8-12 高-低 H-L 28-34 中-低 M-L 18-24 |
0.50 |
40000 | 29 | 26 | 144 | 121 | 0.50 | ||||||
50000 | 34 | 30 | 170 | 144 | 0.43 | ||||||
63000 | 40 | 36 | 201 | 171 | 0.43 | ||||||
90000 | 50 | 46 | 276 | 234 | 0.36 | ||||||
120000 |
10.5 11 13.8 15.75 18 35 37 38.5 |
62 | 56 | 340 | 288 | 0.36 | |||||
150000 | 70 | 60 | 405 | 342 | 0.33 | ||||||
180000 | 80 | 72 | 464 | 387 | 0.33 | ||||||
240000 | 95 | 86 | 595 | 504 | 0.25 |
230kV三绕组有载调压电力变压器 | ||||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range(kv) |
联结组 Connection symbol |
空载损耗 No-load loss (kw) |
负载损耗 Full-load loss (kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
||
高压 HV |
中压 MV |
低压 LV |
||||||
31500 |
220 242±2×2.5% |
69 115 121 |
6.3 6.6 10.5 11 35 37 38.5 |
YNyn0d11 | 44 | 162 |
高-中 H-M 22-24 高-低 H-L 12-14 中-低 M-L 7-9 |
0.77 |
40000 | 50 | 189 | 0.70 | |||||
50000 | 60 | 225 | 0.63 | |||||
63000 | 70 | 261 | 0.63 | |||||
90000 |
10.5 11 35 37 38.5 |
92 | 351 | 0.56 | ||||
120000 | 115 | 432 | 0.56 | |||||
150000 | 135 | 513 | 0.49 | |||||
180000 | 159 | 630 | 0.49 | |||||
240000 | 193 | 780 | 0.45 |
230kV三绕组有载调压自耦电力变压器 | ||||||||
额定容量 Rated capacity (kva) |
电压组合及分接范围 Voltage ratio and tap range(kv) |
联结组 Connection symbol |
空载损耗 No-load loss (kw) |
负载损耗 Full-load loss (kw) |
短路抗阻 Impedance(%) |
空载电流 No-load current (%) |
||
高压 HV |
中压 MV |
低压 LV |
||||||
31500 |
220 242±2×1.25% |
115 121 |
6.3 6.6 10.5 11 35 37 38.5 |
YNyn0d11 | 25 | 108 |
高-中 H-M 28-34 高-低 H-L 8-10 中-低 M-L 18-24 |
0.56 |
40000 | 30 | 132 | 0.56 | |||||
50000 | 36 | 157 | 0.49 | |||||
63000 | 42 | 189 | 0.49 | |||||
90000 |
10.5 11 35 37 38.5 |
51 | 247 | 0.42 | ||||
120000 | 54 | 308 | 0.42 | |||||
150000 | 76 | 365 | 0.35 | |||||
180000 | 85 | 419 | 0.35 | |||||
240000 | 104 | 780 |
0.30 |
使用条件
- 海拔高度小于1000m,空气温度-25℃~40℃,湿度小于90%(+25℃)
- 垂直倾斜度不超过5°,无剧烈振动场所,户外风速不超过35m/s
- 无严重影响变压器绝缘的气体、导电尘埃;无爆炸危险、无腐蚀电气元件的场所
- 超出以上正常使用环境条件,客户可与我公司另行定制解决
WhatsApp:
+86 15853252696(Jack)
+86 135 8926 2999(Martin)
Tel:+86-532-87936206
Fax:+86-532-87936206
地址: 中国·山东省青岛市城阳区中城路638号
© 2021 Copyright By Hengfengyou 版权所有